Cable SizingAhmed Tayeh
How Ambient Temperature Influences Cable Sizing in Australia
Master ambient temperature cable sizing under AS/NZS 3008.1.1:2025; Ka formula, …
Read more: How Ambient Temperature Influences Cable Sizing in AustraliaFree online cable sizing calculator for Australian electrical installations - AS/NZS 3008.1.1:2025 compliant
How it's calculated
The calculator above runs the full CableHero engine, the same one behind saved calculations and PDF reports. These are the checks it makes, with the numbers for the example it opens with.
AS/NZS 3008.1.1:2025 Clause 2.3.1, Section 3 tables; correction factors Clause 3.5
is the tabulated current-carrying capacity of the cable for its installation method (for example Table 3.15 for thermoplastic two-core cables), the design current and the product of the correction factors: grouping (Clause 3.5.2, Tables 3.33 to 3.43), air or soil temperature (Clause 3.5.3, Tables 3.44 and 3.45), depth of laying (Clause 3.5.4, Tables 3.46 and 3.47) and soil thermal resistivity (Clause 3.5.5, Table 3.48). The smallest size that passes, and then passes every check below, is selected.
AS/NZS 3008.1.1:2025 Clauses 2.3.2, 4.3, 4.4 and 4.5
is the a.c. resistance at the conductor's operating temperature (Clause 4.4, read from Tables 4.1 to 4.13), the reactance, the load power factor and the route length in metres. is the three-phase value per Clause 4.3; a single-phase circuit has two conductors carrying the current, so its drop is times it (Clause 4.5). d.c. circuits use (Clause 4.7).
AS/NZS 3000:2018 Clause 3.6.2 limits the drop from the point of supply to any point to 5%, one total shared by the consumer mains, submains and final subcircuits.
AS/NZS 3008.1.1:2025 Clause 5.3; AS/NZS 3000:2018 Clause 5.7.4 and Appendix B5.2.2
The active and earth conductors must withstand the prospective fault current for the clearing time ( from Table 5.1). is the resistance of the active and earth conductors over the route; dividing by 0.8 allows for the 20% of the loop impedance upstream of the circuit. must not exceed , where is the current that trips the device instantly (for example for a Type C circuit breaker), so the device clears an earth fault in time.
Enter your load, supply, cable, installation method, derating and protection above and the calculator selects the smallest cable that passes every AS/NZS 3008.1.1:2025 check, with its derated current rating, voltage drop and fault loop impedance. It is the same engine as the CableHero app, free and without an account. For every field, how to choose the installation picture and derating, and how to read the result, see the step-by-step cable size calculator guide.
Key Principle: The cable's derated current carrying capacity must be greater than or equal to the design current () of the circuit. Mathematically:
45°C ×0.93 · 50°C ×0.85 · 55°C ×0.76
2 circuits ×0.80 · 3 ×0.70 · 4 ×0.65 · 6 ×0.57
0.5m none · 0.8m ×0.97 · 1m ×0.95 · 1.25m ×0.94
AS/NZS 3008.1.1:2025 tabulates the three-phase voltage drop in mV/A.m in its a.c. tables (among Tables 4.14 to 4.31). By Clause 4.5 the single-phase drop is (1.155) times the three-phase one:
Current-carrying capacity of thermoplastic (V-75) multicore cables enclosed in conduit in air at 40°C ambient, from Tables 3.15 (two-core) and 3.18 (three- or four-core), with the voltage drop at 75°C from Tables 4.17 and 4.22 (worst-case power factor).
AS/NZS 3008.1.1:2025 rates aluminium conductors from 16mm².
Frequently Asked Questions