Cable Size Calculator

Free online cable sizing calculator for Australian electrical installations - AS/NZS 3008.1.1:2025 compliant

How to use
Create a free account to save it and download the PDF without a watermark Sign up to save

Electrical Load

Amps

Cable

System Supply

m
V
%

The standard limits are totals from the point of supply, shared with the consumer mains and submains. (AS/NZS 3000 Cl. 3.6.2)

A
s

Installation Method

Derating Factor

Reference ambient per AS/NZS 3008.1.1:2025 (40 °C in air).

Protection

For a final subcircuit with its load spread along it, work out the voltage drop at half the protective device rating, or at the load current if that is smaller (AS/NZS 3000 Cl. 3.6.2, Exception 1).

Cable Size

Active–Circuits in parallel–
Neutral–Circuits in parallel–
Earth–Circuits in parallel1
Spare capacity– A
Operating temperature– °C
Voltage drop– V (–%)
Three-phase SCC– A
Live to earth SCC– A
Fault loop impedance– Ω
Protection typeMCB
Breaker rating32 A
Cable derated current0.8 A
Rated current– A
Cable resistance– Ω/km
Cable reactance– Ω/km
Min active conductor– mm²
Min earth conductor– mm²
Internal impedance– Ω
External impedance– Ω

How it's calculated

The AS/NZS 3008.1.1:2025 Method

The calculator above runs the full CableHero engine, the same one behind saved calculations and PDF reports. These are the checks it makes, with the numbers for the example it opens with.

1. Current-carrying capacity

AS/NZS 3008.1.1:2025 Clause 2.3.1, Section 3 tables; correction factors Clause 3.5

is the tabulated current-carrying capacity of the cable for its installation method (for example Table 3.15 for thermoplastic two-core cables), the design current and the product of the correction factors: grouping (Clause 3.5.2, Tables 3.33 to 3.43), air or soil temperature (Clause 3.5.3, Tables 3.44 and 3.45), depth of laying (Clause 3.5.4, Tables 3.46 and 3.47) and soil thermal resistivity (Clause 3.5.5, Table 3.48). The smallest size that passes, and then passes every check below, is selected.

2. Voltage drop

AS/NZS 3008.1.1:2025 Clauses 2.3.2, 4.3, 4.4 and 4.5

is the a.c. resistance at the conductor's operating temperature (Clause 4.4, read from Tables 4.1 to 4.13), the reactance, the load power factor and the route length in metres. is the three-phase value per Clause 4.3; a single-phase circuit has two conductors carrying the current, so its drop is times it (Clause 4.5). d.c. circuits use (Clause 4.7).

AS/NZS 3000:2018 Clause 3.6.2 limits the drop from the point of supply to any point to 5%, one total shared by the consumer mains, submains and final subcircuits.

3. Short circuit and fault loop

AS/NZS 3008.1.1:2025 Clause 5.3; AS/NZS 3000:2018 Clause 5.7.4 and Appendix B5.2.2

The active and earth conductors must withstand the prospective fault current for the clearing time ( from Table 5.1). is the resistance of the active and earth conductors over the route; dividing by 0.8 allows for the 20% of the loop impedance upstream of the circuit. must not exceed , where is the current that trips the device instantly (for example for a Type C circuit breaker), so the device clears an earth fault in time.

How to Use This Cable Size Calculator

Enter your load, supply, cable, installation method, derating and protection above and the calculator selects the smallest cable that passes every AS/NZS 3008.1.1:2025 check, with its derated current rating, voltage drop and fault loop impedance. It is the same engine as the CableHero app, free and without an account. For every field, how to choose the installation picture and derating, and how to read the result, see the step-by-step cable size calculator guide.

Cable Sizing Basics

Understanding Current Carrying Capacity

  • Conductor material - Copper has approximately 1.6 times the conductivity of aluminium
  • Conductor cross-sectional area - Larger cables can carry more current
  • Insulation type - thermoplastic V-75 and V-90 (rated at 75°C), cross-linked X-90 (90°C) and X-HF-110 (110°C) have different temperature ratings
  • Installation method - How well the cable can dissipate heat

Key Principle: The cable's derated current carrying capacity must be greater than or equal to the design current () of the circuit. Mathematically:

Derating Factors Explained

Ambient Temperature (Table 3.44, 75°C cables)

45°C ×0.93 · 50°C ×0.85 · 55°C ×0.76

Grouping/Bunching (Table 3.33, bunched on a surface or enclosed)

2 circuits ×0.80 · 3 ×0.70 · 4 ×0.65 · 6 ×0.57

Depth of Laying (Table 3.46, buried direct, up to 50mm²)

0.5m none · 0.8m ×0.97 · 1m ×0.95 · 1.25m ×0.94

Voltage Drop Calculations

  • Whole installation: maximum 5% from the point of supply to any point (AS/NZS 3000:2018 Clause 3.6.2), shared between consumer mains, submains and final subcircuits
  • Dedicated substation: up to 7% where the point of supply is a substation on the premises dedicated to the installation

AS/NZS 3008.1.1:2025 tabulates the three-phase voltage drop in mV/A.m in its a.c. tables (among Tables 4.14 to 4.31). By Clause 4.5 the single-phase drop is (1.155) times the three-phase one:

Cable Selection Methodology

  1. Determine the design current
  2. Select the protective device rating
  3. Identify installation conditions
  4. Calculate the total derating factor
  5. Select the minimum cable size with
  6. Check voltage drop against the limits
  7. Verify fault current withstand

AS/NZS 3008.1.1:2025 Cable Current Ratings Reference

Current-carrying capacity of thermoplastic (V-75) multicore cables enclosed in conduit in air at 40°C ambient, from Tables 3.15 (two-core) and 3.18 (three- or four-core), with the voltage drop at 75°C from Tables 4.17 and 4.22 (worst-case power factor).

Copper Conductors (V-75)
Size (mm²)Two-core (A)Three/four-core (A)Vc three-phase (mV/A.m)Vc single-phase (mV/A.m)
1131144.751.6
1.5161428.633
2.5232015.618
430259.7111.2
639336.497.49
1052443.864.46
1668582.432.81
2590761.541.78
35112941.111.28
501331120.8270.955
701701420.5810.671
952041770.4280.494
1202412020.3480.402
1502712280.2930.338
1853132630.2470.285
2403643160.2060.238
3004243560.1820.21
Aluminium Conductors (V-75)
Size (mm²)Two-core (A)Three/four-core (A)Vc three-phase (mV/A.m)Vc single-phase (mV/A.m)
1652454.044.66
2570592.542.93
3587731.842.12
50103871.361.57
701321110.9471.09
951581370.690.797
1201871570.5510.636
1502101770.4560.527
1852442060.3720.43
2402852480.2950.341
3003332810.2490.288

AS/NZS 3008.1.1:2025 rates aluminium conductors from 16mm².

Ambient Air Temperature Factors (Table 3.44)
Ambient Temp75°C (V-75, V-90)90°C (X-90)110°C (X-HF-110)
30°C1.131.11.07
35°C1.071.051.04
40°C111
45°C0.930.950.96
50°C0.850.890.93
55°C0.760.840.89
60°C0.650.770.85

Frequently Asked Questions

Cable Sizing Questions Answered

How do I calculate cable size for my electrical installation?

To calculate cable size according to AS/NZS 3008.1.1:2025, you need to: 1) Determine your load current, 2) Identify the installation method, 3) Apply derating factors for temperature, grouping, and burial depth, 4) Select a cable with adequate current carrying capacity, 5) Verify voltage drop is within the 5% limit, and 6) Check fault current withstand capability. Our calculator above does steps 3 to 6 for you, with every AS/NZS 3008.1.1:2025 derating factor.

What cable size do I need for 32 Amps?

For a 32 Amp single-phase load on copper two-core thermoplastic (V-75) cable at 40°C, AS/NZS 3008.1.1:2025 Table 3.15 gives 4mm² unenclosed (34 A) or 6mm² enclosed in conduit (39 A). Voltage drop then sets the size on longer runs: at 230 V and 32 A, 4mm² reaches 5% at about 32m, 6mm² at about 48m and 10mm² at about 80m. Grouping with other circuits or a hotter ambient needs a larger size. Use our calculator for your specific conditions.

What cable size do I need for 20 Amps?

For a 20 Amp single-phase circuit, 2.5mm² copper two-core cable carries 23 A enclosed in conduit (AS/NZS 3008.1.1:2025 Table 3.15) and keeps voltage drop within 5% of 230 V up to about 32m; 4mm² goes to about 51m. If the cable is bunched with other circuits or in high ambient temperatures, derating may require upsizing to 4mm² regardless of length.

What is AS/NZS 3008?

AS/NZS 3008 (Electrical installations - Selection of cables) is the Australian/New Zealand Standard that specifies requirements for selecting cables. It covers current carrying capacity tables for different installation methods, voltage drop calculation from cable resistance and reactance (with tabulated mV/A.m values), derating factors for various conditions, and short-circuit performance. Part 1.1 (current edition AS/NZS 3008.1.1:2025) covers cables for voltages up to and including 0.6/1 kV a.c. and 1500 V d.c. under typical Australian installation conditions.

What are cable derating factors?

Derating factors reduce a cable's rated current capacity based on installation conditions that affect heat dissipation. Key factors in AS/NZS 3008.1.1:2025 include: ambient air and soil temperature (Tables 3.44 and 3.45) - higher temps mean more derating, cable grouping (Tables 3.33 to 3.43) - multiple cables together generate more heat, depth of laying (Tables 3.46 and 3.47) - deeper burial reduces heat dissipation, and soil thermal resistivity (Table 3.48) - affects buried cable ratings. All applicable factors are multiplied together.

What is the maximum voltage drop allowed in Australia?

AS/NZS 3000:2018 Clause 3.6.2 limits the voltage drop from the point of supply to any point in the installation to 5% of the nominal voltage. That is one total for consumer mains, submains and final subcircuits together, so the designer decides how to share it. It may be 7% where the installation has its own substation on the premises, and extra-low voltage installations are limited to 10% (Clause 7.5.7). Your distributor's service and installation rules may set further limits, such as on consumer mains, so check them.

Copper vs aluminium cables - which should I use?

Copper has about 1.6x the conductivity of aluminium, so copper cables are smaller for the same current capacity. Copper is preferred for most installations due to better conductivity, easier termination, and no galvanic corrosion issues. Aluminium is mainly used for large feeders (95mm² and above) where cost savings are significant. Aluminium requires special terminations and is not recommended for sizes below 16mm².

How does installation method affect cable sizing?

Installation method significantly affects current ratings because it determines heat dissipation capability. Cables in free air have the highest ratings. Cables in conduit have reduced ratings due to restricted air flow. Buried cables ratings depend on soil conditions and depth. Cables on trays have good ratings with proper spacing. AS/NZS 3008.1.1:2025 provides separate current rating tables for each installation method.

Reviewed by Ahmed Tayeh, electrical engineer at CableHero. The calculator is a design aid: the designer remains responsible for checking the installation against the standards.

Guides

Learn the method

How to use this calculator

Every card of the cable size calculator, from the load to the protection, and how to read the checks it runs.

Read the guide: How to use the cable size calculator (AS/NZS 3008.1.1:2025)

More free tools

Other calculators

Ready for Professional Cable Sizing?

Save your AS/NZS 3008.1.1:2025 calculations to projects and download detailed PDF reports. Free to start.