How It's Calculated
A motor's kW rating is its output at the shaft. The current it draws depends on the electrical input, which is the output divided by the efficiency, and on the power factor:
Three-phase: I = P × 1000 / (√3 × V × η × cos φ)
Single-phase: I = P × 1000 / (V × η × cos φ)
where P is the rated output in kW, V the line-to-line voltage (three-phase) or the terminal voltage (single-phase), η the full load efficiency as a fraction and cos φ the full load power factor. These are the formulas in the Schneider Electric Electrical Installation Guide (“Induction motors”).
Worked Example
An 11 kW three-phase motor on 400 V with an efficiency of 89% and a power factor of 0.85:
- Input power = 11 / 0.89 = 12.36 kW
- Input apparent power = 12.36 / 0.85 = 14.54 kVA
- I = 14,541 / (√3 × 400) = 21.0 A
IEC 60947-4-1 Annex G lists 22 A for an 11 kW motor at 400 V; the difference is the efficiency and power factor the table assumes.