Motor Full Load Current Calculator
Convert a motor's kW rating to amps for single and three-phase supplies
How It's Calculated
A motor's kW rating is its output at the shaft. The current it draws depends on the electrical input, which is the output divided by the efficiency, and on the power factor:
where is the rated output in kW, the line-to-line voltage (three-phase) or the terminal voltage (single-phase), the full load efficiency as a fraction and the full load power factor. These are the formulas in the Schneider Electric Electrical Installation Guide (“Induction motors”).
Worked Example
An 11 kW three-phase motor on 400 V with an efficiency of 89% and a power factor of 0.85:
- Input power = 11 / 0.89 = 12.36 kW
- Input apparent power = 12.36 / 0.85 = 14.54 kVA
- 21.0 A
IEC 60947-4-1 Annex G lists 22 A for an 11 kW motor at 400 V; the difference is the efficiency and power factor the table assumes.
Typical Motor Full Load Currents
Rated operational currents of standard three-phase motors from IEC 60947-4-1 Annex G, as reproduced in the Schneider Electric Electrical Installation Guide. Use them as guidance before the motor is selected; the nameplate current governs.