Three Phase Power Calculator
Real, reactive and apparent power from the line current, voltage and power factor
Free tool, no sign-up needed Sign up free
How It's Calculated
For a balanced three-phase load, with the line-to-line voltage, the line current and the angle whose cosine is the power factor:
- Apparent power: kVA
- Real power: kW
- Reactive power: kVAr
Each phase carries a third of each total. In star each phase sees and carries the line current; in delta each phase sees and carries . Either way .
Worked Example
A star-connected load drawing 50 A per line from a 400 V supply at a power factor of 0.85:
- S = 1.732 × 400 × 50 / 1000 = 34.64 kVA
- P = 34.64 × 0.85 = 29.44 kW
- φ = arccos 0.85 = 31.8°, Q = 34.64 × sin 31.8° = 18.25 kVAr
- Per phase: 9.81 kW, 6.08 kVAr, 11.55 kVA at 230.9 V