Arc Flash Calculator
Incident energy and arc flash boundary for 208 to 600 V equipment, IEEE 1584-2018
How It's Calculated
IEEE 1584-2018 fits its equations to arc tests in five electrode configurations. Below 600 V the method takes four steps:
- Arcing current at 600 V, Eq. (1), with the bolted fault current in kA and the gap in mm:
- Arcing current at the system voltage in kV, Eq. (25), and the reduced arcing current from the variation factor , Eq. (2):
- Enclosure correction, Eqs. (11) to (15): the enclosure's width and height give an equivalent size in inches, and a quadratic in it gives (1 for open air). Bigger boxes let the arc spread and lower the energy; shallow boxes concentrate it.
- Incident energy and boundary, Eqs. (6) and (10), with in ms and the working distance in mm. The arc flash boundary is the distance at which falls to 1.2 cal/cm²:
Both arcing current cases are run with the clearing time at that current, and the higher incident energy is the result. The 2700 V and 14.3 kV equations of the standard are for medium voltage and are not used below 600 V.
Assumptions: a three-phase arc in a three-phase, 50 or 60 Hz AC system from 208 to 600 V (IEEE 1584-2018 4.2); bolted fault current from 0.5 to 106 kA; gaps from 6.35 to 76.2 mm; working distance at least 305 mm; enclosure width at least four times the gap, with heights and widths above 1244.6 mm taken as 1244.6 mm (4.8.1). The PPE category is a guide from the NFPA 70E thresholds (1.2, 4, 8, 25 and 40 cal/cm²); select clothing with an arc rating at least equal to the incident energy.
Worked Example
IEEE 1584-2018 Annex D.2: a 480 V switchboard with 45 kA bolted fault current, VCB conductors with a 32 mm gap in a 610 × 610 × 254 mm enclosure, a working distance of 609.6 mm, clearing in 61.3 ms at the full arcing current and 319 ms at the reduced one:
- , so at 480 V
- Equivalent enclosure size 24.016 in (typical),
- Full case: (2.77 cal/cm²), boundary 1,029 mm
- , so
- Reduced case: (12.70 cal/cm²), boundary 2,669 mm
The reduced arcing current takes 319 ms to clear instead of 61.3 ms, so it gives over four times the energy and governs. The calculator reproduces every figure of Annex D.2. As a guide that is PPE category 3 (arc rating of at least 25 cal/cm²).
Incident Energy by Clearing Time
Incident energy in cal/cm² for a 415 V switchboard: VCB, 32 mm gap, 508 mm enclosure, 609.6 mm working distance, full arcing current. The clearing time matters more than the fault level.
Frequently Asked Questions