Fault Loop Impedance Calculator

Earth fault-loop impedance against the AS/NZS 3000:2018 maximum for B, C and D curve circuit breakers

How to use

Earth fault-loop impedance of a final subcircuit or submain, checked against the maximum for an MCB to AS/NZS 3000:2018.

Supply

V
kA

Sets the source impedance for the fault current only

Protection

Cable

m

Fault Loop

Enter the voltage, fault level and route length to check the fault loop.

How it's calculated

Earth fault-loop impedance, step by step

The calculator works the loop the way AS/NZS 3000:2018 Appendix B5 does, with the conductor data of AS/NZS 3008.1.1:2025.

Maximum loop impedance

phase-to-earth voltage, V (line voltage / √3 on a three-phase circuit)
instantaneous trip current: In × 4 (B), 7.5 (C) or 12.5 (D)

Cable impedance (active + earth)

√(Rc² + Xc²) of the active and the earth, Ω/km
route length, m
parallel runs

Circuit loop impedance

share of Uo at the circuit's origin during a fault (Appendix B5.2.2)

Maximum route length

grows in proportion to the length, so the limit scales straight from the calculated value.

Standards referenced

  • AS/NZS 3000:2018 Clause 5.7 (automatic disconnection) and Clause 8.3.9 (verification)
  • AS/NZS 3000:2018 Appendix B5 and Table 8.1 (maximum Zs for circuit breakers)
  • AS/NZS 3000:2018 Table 5.1 (minimum earthing conductor size)
  • AS/NZS 3008.1.1:2025 Table 4.1 (reactance) and Tables 4.5 and 4.7 (a.c. resistance of single-core and multicore cables)

Worked example: 2.5 mm² TPS on a C20 MCB

A 230 V single-phase final subcircuit in 2.5 mm² two-core and earth V-75 TPS, 40 m long, protected by a 20 A C curve MCB.

  1. 1. Maximum Zs
  2. 2. Earth size (Table 5.1)
  3. 3. Active Rc at 75 °C
  4. 4. Cable impedance
  5. 5. Circuit Zs
  6. 6. Maximum length

Zs is 0.901 Ω, below the 1.533 Ω maximum, so the MCB trips in time. The circuit could run to about 68 m, the same length AS/NZS 3000:2018 Table B1 gives for 2.5 mm² on a C20.

Frequently Asked Questions

Fault Loop Impedance Questions Answered

What is earth fault-loop impedance?

It is the impedance of the path a fault current takes from the supply, through the active conductor to the fault, back along the protective earth and the supply neutral. AS/NZS 3000:2018 Clause 5.7 requires it to be low enough that the fault current trips the protective device within the disconnection time of Clause 5.7.4 (0.4 s for final subcircuits up to 63 A supplying socket-outlets or hand-held equipment, 5 s for others).

How is the maximum Zs worked out for an MCB?

Zs maximum = Uo / Ia, where Uo is the nominal phase-to-earth voltage (230 V) and Ia the current that operates the device instantaneously. For MCBs the calculator takes Ia as 4, 7.5 and 12.5 times the rating for B, C and D curves, the multiples behind the AS/NZS 3000:2018 Table 8.1 values. A C20 MCB at 230 V allows 230 / 150 = 1.53 Ω.

Why is the cable impedance divided by 0.8?

AS/NZS 3000:2018 Appendix B5.2.2 assumes that 80% of the nominal voltage is available at the circuit's origin during a fault; the other 20% is lost in the supply. Dividing the circuit's own active plus earth impedance by 0.8 gives the total loop impedance compared with Uo / Ia, without needing a measured external impedance.

Which conductor resistance is used?

The AS/NZS 3008.1.1:2025 a.c. resistance at the insulation's maximum operating temperature (75 °C for V-75 PVC, 90 °C for X-90 XLPE) for both the active and the earth, plus the tabulated reactance. That is the hot, worst-case loop the device must still clear.

Does the calculated value replace testing?

No. AS/NZS 3000:2018 Clause 8.3.9 requires the fault loop to be verified when the installation is tested. The calculation is for design: it tells you before installation whether the cable and earth sizes and the route length work with the chosen device.

What do I do if the circuit fails?

Shorten the route, increase the earth conductor (it is often smaller than the active), increase the active size, or use a device with a lower instantaneous trip current, such as a B curve or an RCD where permitted. The maximum length in the results shows how far the circuit can run as it is.

Reviewed by Suheib Sherif, electrical engineer at CableHero. The calculator is a design aid: the designer remains responsible for checking the installation against the standards.

Guides

Learn the method

How to use this calculator

Check that a circuit's earth fault loop impedance lets the protective device disconnect in time.

Read the guide: How to use the fault loop impedance calculator