kVA Calculator
Convert between kVA, kW and amps at any power factor
Convert
e.g. a transformer, generator or UPS rating
Supply
Line-to-line, 400 V in Australia and New Zealand
0.8 is a common assumption; 1 for resistive loads such as heaters
Conversion
Enter a value in kVA to convert it.
How It's Calculated
Apparent power (kVA), real power (kW) and reactive power (kVAr) form the power triangle, with the power factor as the cosine of its angle:
- kW = kVA × cos φ, kVA = kW / cos φ
- kVAr = √kVA² − kW²
- Three-phase: I = kVA × 1000 / (√3 × VL); single-phase: I = kVA × 1000 / V
The current depends only on the kVA and the voltage, so starting from kW goes through the power factor first. Three-phase values assume a balanced load.
Worked Example
A 100 kVA load on 400 V three-phase at a power factor of 0.8:
- kW = 100 × 0.8 = 80 kW
- kVAr = √(100² − 80²) = 60 kVAr
- I = 100 × 1000 / (1.732 × 400) = 144.3 A per line
Frequently Asked Questions
kVA Questions Answered
How do I convert kVA to kW?
Multiply by the power factor: kW = kVA × cos φ. 100 kVA at a power factor of 0.8 is 80 kW. Going the other way, kVA = kW / cos φ.
How do I convert kVA to amps?
For three-phase divide by √3 and the line-to-line voltage: I = kVA × 1000 / (√3 × V). For single-phase divide by the voltage: I = kVA × 1000 / V. 100 kVA at 400 V three-phase is 144 A per line.
How many amps per kVA?
About 1.44 A per kVA at 400 V three-phase and 4.35 A per kVA at 230 V single-phase. The power factor does not change this: amps follow the kVA, not the kW.
Why are transformers and generators rated in kVA?
Their losses and heating depend on the current and the voltage, not on how much of the current does useful work. The manufacturer cannot know the load's power factor, so the rating is the apparent power the windings can carry.
What is kVAr?
Reactive power, the part of the apparent power that flows back and forth to build magnetic and electric fields without doing work. kVA² = kW² + kVAr². Capacitor banks supply kVAr locally to lift the power factor.
What size transformer or generator do I need for a load?
Convert the load's maximum demand to kVA, then pick the next standard size above it with allowance for growth. A generator also needs checking for motor starting, which the generator sizing calculator covers.
Reviewed by Ahmed Tayeh, electrical engineer at CableHero. The calculator is a design aid: the designer remains responsible for checking the installation against the standards.
More free tools
Other calculators
- Cable Size Calculator Current rating, derating and voltage drop to AS/NZS 3008.1.1:2025
- Voltage Drop Calculator Drop in volts and percent against the AS/NZS 3000:2018 5% limit
- Voltage Rise Calculator Rise from solar PV, generators and other exporting equipment
- Maximum Demand Calculator AS/NZS 3000:2018 Appendix C, Tables C1 to C3
- Conduit Size Calculator Conduit fill to AS/NZS 3000:2018 Appendix C
- Protection Coordination Calculator Discrimination, cable withstand and disconnection to AS/NZS 3000:2018
- PV String Voltage Calculator Voc and Vmp at site temperatures, AS/NZS 5033:2021 limits
- Battery Storage Sizing Calculator Usable kWh, modules, inverter and cable currents, AS/NZS 5139 voltage class
- Single Line Diagram Software Draw SLDs linked to your cable calculations
- Fault Loop Impedance Calculator Zs against Uo / Ia for B, C and D curve MCBs, AS/NZS 3000:2018
- Cable Short-Circuit Calculator Adiabatic I²t = K²S² withstand, AS/NZS 3008.1.1:2025 Table 5.1
- Earth Cable Size Calculator Protective earth to AS/NZS 3000:2018 Table 5.1, with the fault check
- Cable Derating Calculator Grouping, temperature, depth and soil factors, AS/NZS 3008.1.1:2025
- Cable Pulling Calculator Pulling tension and sidewall pressure to IEEE Std 1185-2019
- Motor Full Load Current Calculator Motor kW to amps, with IEC 60947-4-1 typical currents
- Power Factor Correction Calculator Capacitor bank kVAr in whole steps, and the current saved
- Transformer Fault Current Calculator Prospective fault current at the LV terminals, IEC 60909 simplified
- Generator Sizing Calculator Generator kVA from the running load and motor starting
- Arc Flash Calculator Incident energy and arc flash boundary, IEEE 1584-2018 for 208 to 600 V
- kW to Amps Calculator Kilowatts to amps for single-phase, three-phase and DC
- Amps to kW Calculator Amps to kilowatts for single-phase, three-phase and DC
- Three Phase Power Calculator kW, kVAr and kVA in total and per phase, star or delta
- Ohm's Law Calculator Any two of voltage, current, resistance and power
Sizing a Generator?
Add the running loads and the largest motor start to get the generator kVA.