Transformer Fault Current Calculator
Prospective three-phase fault current at the LV terminals, IEC 60909 simplified
How It's Calculated
With an infinite (stiff) source, the transformer's impedance alone limits the fault current:
where is the rated power, the LV nominal voltage, the short-circuit impedance as a fraction and the IEC 60909-0 voltage factor. With a finite source the network impedance, referred to the LV side, is added in series (IEC 60909-0, clause 6.2, for a network with no other data):
split into and by the transformer's
Assumptions: a bolted three-phase fault at the LV terminals; no cable, busbar or arc impedance; no contribution from running motors; nominal tap; and no impedance correction factor , which IEC 60909-0 applies to network transformers and which raises the result by a few percent. For a design of record, run a full IEC 60909 study.
Worked Example
A 1000 kVA, 400 V transformer with 5% impedance and X/R of 5, fed from a 250 MVA source, :
- Full load current =
- Source: ()
- Transformer: ()
- Total , so 26.74 kA
- , so
With an infinite source the same transformer gives 28.87 kA, so the 250 MVA network takes about 7% off the fault current.
Fault Current by Transformer Size
Prospective fault current at 400 V with an infinite source and c = 1.0, for typical impedances. Use the nameplate impedance of the actual transformer.