Power Factor Correction Calculator

Size the capacitor bank in kVAr and see the current it saves

Free tool, no sign-up needed Sign up free

Load

kW

The real power of the load, e.g. from the maximum demand

V

Line-to-line, e.g. 400 V

Hz

For the capacitance; 50 Hz in Australia

Power Factor

cos φ

From the bill, a power analyser or the load's data

cos φ

Commonly 0.95, or the supplier's tariff threshold

kVAr

The bank is built from whole steps; clear it for the exact value

Capacitor Bank

Enter the load's active power and present power factor to size the capacitor bank.

How It's Calculated

A capacitor bank supplies reactive power locally, so the supply only carries the load's active power and what reactive power remains. The reactive power to add is set by the change in the power factor angle:

where is the active power in kW, the angle of the existing power factor and the angle of the target. The bank is rounded up to whole capacitor steps, and the corrected power factor is worked back from what is installed. The current follows the apparent power:

The capacitance comes from : for a three-phase delta bank each of the three capacitors takes a third of the kVAr across the line voltage. The method is the one in the Schneider Electric Electrical Installation Guide, chapter L (“Power factor correction”); capacitor ratings themselves are covered by IEC 60831-1.

Worked Example

A 200 kW three-phase load on 400 V at a power factor of 0.75, corrected to 0.95 with 25 kVAr steps:

  • , rounded up to 125 kVAr
  • Corrected power factor = 0.969
  • Current 384.9 A → 298.1 A, a 22.6% reduction
  • Capacitance per phase (delta) = 829 µF

Frequently Asked Questions

Power Factor Correction Questions Answered

How do I calculate the kVAr needed for power factor correction?

Multiply the active power by the difference between the tangents of the existing and target power factor angles: Qc = P × (tan φ1 − tan φ2). Lifting a 200 kW load from 0.75 to 0.95 needs about 111 kVAr.

What power factor should I correct to?

0.95 lagging is the usual target. Network tariffs differ: some set a minimum power factor (often 0.9 or 0.95), others bill demand in kVA so every improvement lowers the charge, so check the supplier's tariff first. Correcting all the way to 1.0 gains little and risks a leading power factor at light load.

Why does the bank come out larger than the calculated kVAr?

Capacitor banks are built from fixed steps, commonly 12.5, 25 or 50 kVAr. The calculator rounds up to whole steps so the bank reaches the target, then reports the power factor the installed bank actually gives.

How much does power factor correction reduce the current?

For the same active power, the current falls in proportion to the power factors: I2 = I1 × cos φ1 / cos φ2. Going from 0.75 to 0.95 cuts the current by about 21%, which frees capacity in transformers, switchboards and cables and reduces their losses.

Do harmonics affect capacitor bank selection?

Yes. Capacitors lower the system's resonant frequency and can amplify harmonics from variable speed drives, UPSs and LED drivers. Where non-linear loads are significant, use a detuned bank with series reactors (typically tuned to 189 Hz on a 50 Hz system, 7% detuning) and check the harmonic voltage distortion.

Reviewed by Suheib Sherif, electrical engineer at CableHero. The calculator is a design aid: the designer remains responsible for checking the installation against the standards.

More free tools

Other calculators

Start From the Maximum Demand

Work out the installation's maximum demand to AS/NZS 3000:2018 Appendix C, then size the correction against it.