Amps to kW Calculator
Convert a current in amps to kilowatts for single-phase, three-phase and DC supplies
Supply
Line-to-line, 400 V in Australia and New Zealand
0.8 is a common assumption; 1 for resistive loads such as heaters
Current
The current in each line of a balanced load
Power
Enter the current in amps to get the power.
How It's Calculated
Voltage times current gives the apparent power; the power factor turns that into the real power in kW:
- Three-phase: P = √3 × VL × I × cos φ / 1000, with VL the line-to-line voltage and I the line current
- Single-phase: P = V × I × cos φ / 1000
- DC: P = V × I / 1000
The apparent power is S = √3 × VL × I / 1000 (or V × I / 1000 single-phase) and the reactive power Q = √S² − P². The three-phase formula assumes a balanced load.
Worked Example
A 32 A load on a 400 V three-phase supply at a power factor of 0.8:
- S = 1.732 × 400 × 32 / 1000 = 22.17 kVA
- P = 22.17 × 0.8 = 17.74 kW
- Q = 13.30 kVAr
Frequently Asked Questions
Amps to kW Questions Answered
How do I convert amps to kW for three-phase?
Multiply √3 by the line-to-line voltage, the line current and the power factor, then divide by 1000: P = √3 × V × I × cos φ / 1000. 32 A at 400 V and a power factor of 0.8 is about 17.7 kW.
How do I convert amps to kW for single-phase?
Multiply the voltage, the current and the power factor, then divide by 1000: P = V × I × cos φ / 1000. 32 A at 230 V is 7.36 kW at unity power factor, or 5.89 kW at 0.8.
How many kW is a 32 A three-phase supply?
A 32 A, 400 V three-phase supply delivers 22.2 kVA, which is 22.2 kW for a resistive load or about 17.7 kW at a power factor of 0.8. That is the capacity at full current; the usable load also depends on the protection and the maximum demand.
What is the difference between kW and kVA?
kVA is the apparent power, voltage times current, and sets the heating in cables and transformers. kW is the real power that does work. The power factor is the ratio kW / kVA, so for a resistive load they are equal.
Should I use the line or phase voltage?
For three-phase use the line-to-line voltage (400 V in Australia and New Zealand) with the line current; the √3 in the formula accounts for the three phases. For single-phase use the phase-to-neutral voltage (230 V).
Does a clamp meter reading give the kW?
It gives the current. Multiply by the voltage and, for AC, the power factor. Without a power analyser the power factor is an estimate, so the result is the apparent power in kVA at best and the kW is approximate.
Reviewed by Ahmed Tayeh, electrical engineer at CableHero. The calculator is a design aid: the designer remains responsible for checking the installation against the standards.
More free tools
Other calculators
- Cable Size Calculator Current rating, derating and voltage drop to AS/NZS 3008.1.1:2025
- Voltage Drop Calculator Drop in volts and percent against the AS/NZS 3000:2018 5% limit
- Voltage Rise Calculator Rise from solar PV, generators and other exporting equipment
- Maximum Demand Calculator AS/NZS 3000:2018 Appendix C, Tables C1 to C3
- Conduit Size Calculator Conduit fill to AS/NZS 3000:2018 Appendix C
- Protection Coordination Calculator Discrimination, cable withstand and disconnection to AS/NZS 3000:2018
- PV String Voltage Calculator Voc and Vmp at site temperatures, AS/NZS 5033:2021 limits
- Battery Storage Sizing Calculator Usable kWh, modules, inverter and cable currents, AS/NZS 5139 voltage class
- Single Line Diagram Software Draw SLDs linked to your cable calculations
- Fault Loop Impedance Calculator Zs against Uo / Ia for B, C and D curve MCBs, AS/NZS 3000:2018
- Cable Short-Circuit Calculator Adiabatic I²t = K²S² withstand, AS/NZS 3008.1.1:2025 Table 5.1
- Earth Cable Size Calculator Protective earth to AS/NZS 3000:2018 Table 5.1, with the fault check
- Cable Derating Calculator Grouping, temperature, depth and soil factors, AS/NZS 3008.1.1:2025
- Cable Pulling Calculator Pulling tension and sidewall pressure to IEEE Std 1185-2019
- Motor Full Load Current Calculator Motor kW to amps, with IEC 60947-4-1 typical currents
- Power Factor Correction Calculator Capacitor bank kVAr in whole steps, and the current saved
- Transformer Fault Current Calculator Prospective fault current at the LV terminals, IEC 60909 simplified
- Generator Sizing Calculator Generator kVA from the running load and motor starting
- Arc Flash Calculator Incident energy and arc flash boundary, IEEE 1584-2018 for 208 to 600 V
- kW to Amps Calculator Kilowatts to amps for single-phase, three-phase and DC
- kVA Calculator kVA, kW and amps at any power factor
- Three Phase Power Calculator kW, kVAr and kVA in total and per phase, star or delta
- Ohm's Law Calculator Any two of voltage, current, resistance and power
Add Up the Whole Installation
Work out the maximum demand to AS/NZS 3000 Appendix C before choosing the supply.