Earth Cable Size Calculator
Minimum copper protective earth to AS/NZS 3000:2018 Table 5.1, with the fault-current check
Minimum copper protective earthing conductor for a circuit, to AS/NZS 3000:2018 Table 5.1 and the adiabatic check.
How it's calculated
Sizing the protective earth
Two rules, and the larger answer wins: the table minimum, and the size that carries the earth fault current until the device clears it.
Standards referenced
- AS/NZS 3000:2018 Clause 5.3.3.1 and Table 5.1 (size of protective earthing conductors)
- AS/NZS 3000:2018 Clause 5.3.3.1.2 (parallel conductors)
- AS/NZS 3008.1.1:2025 Clause 5.3, Equation 5.3 and Table 5.1 (K)
Worked example: 2 × 95 mm² single-core submain
A submain of 2 parallel runs of 95 mm² copper X-90 single-core cables, with a 20 kA prospective earth fault current cleared in 0.2 s.
- 1. Total active area
- 2. Table 5.1 row
- 3. Table 5.1 earth
- 4. K for the earth
- 5. Adiabatic minimum
The fault needs 62.6 mm², less than the table's 95 mm², so Table 5.1 governs: install a 95 mm² copper earth.
Reference
Minimum earth sizes (Table 5.1)
Copper protective earthing conductor, mm², for each active conductor size.