How to use the earth cable size calculator

Pick the protective earth from the active size, then check it against the fault it must carry.

Updated 1 Nov 2026 · Reviewed by Suheib Sherif, electrical engineer

What the earth cable size calculator does

The protective earth carries the fault current back to the source so the protective device can trip. It must be large enough to meet the minimum in AS/NZS 3000:2018 Table 5.1, and large enough not to overheat while it carries the fault. The free earth cable size calculator does both: it reads the Table 5.1 earth size from the active conductors, then, if you give it the earth fault current and clearing time, runs the adiabatic check and raises the earth when the fault needs more copper.

Use the earth cable size calculation when you:

  • size the earth for a submain or a single-core feeder where the earth is a separate cable;
  • size an earth for parallel runs, which Table 5.1 reads by their total area;
  • check whether the earth core in a multicore cable is enough for the fault level at the switchboard.

Before you start: inputs to collect

  • Active conductors: multicore or single-core, copper or aluminium, the active size and the number of parallel runs.
  • Insulation of the actives: the earth runs with them and starts the fault at their temperature.
  • Prospective earth fault current in kA and the protective device's clearing time at that current, for the fault check.

How to size an earth cable in Australia, step by step

  1. 1

    Describe the active conductors

    In the Active Conductors card set Construction to Multicore or Single-core and choose the Conductor, Copper or Aluminium. Table 5.1 has a separate column for aluminium actives; the earth it gives is still copper. Pick the Active size and enter the number of Parallel runs. The hint reminds you that Table 5.1 is read with the total active area.

    Earth cable size calculator with the Active Conductors card set to two parallel runs of 95 mm² single-core copper
  2. 2

    Turn on the earth fault check

    The Earth Fault card has a switch in its header. With it off, the calculator uses Table 5.1 only. Switch it on and three fields appear: Insulation (the actives' insulation, which sets the earth's starting temperature), Prospective earth fault current in kA and Clearing time in seconds.

    Earth Fault card switched on with insulation, prospective earth fault current and clearing time, and the Earth Conductor result beside it
  3. 3

    Read the earth to install

    The Earth Conductor card on the right updates as you type; the next section explains it.

Reading the earth conductor result

The headline is Earth: followed by the size to install, for example 95 mm² copper, with the actives it serves underneath. The checks list shows the Table 5.1 line and, when the fault check is on, a Fault current line with the adiabatic minimum and K, marked governs when it is the larger. Then:

  • Total active area: the active size times the parallel runs, the value Table 5.1 is read with.
  • Table 5.1 earth: the minimum copper earth for that area.
  • and Adiabatic minimum (): shown when the fault check is on.
  • Earth to install: the larger of the two, as a standard size.

The grey note is a reminder that the earth also has to keep the fault loop impedance low enough; check that with the fault loop impedance calculator.

Worked examples: Table 5.1 and the fault check

A submain in parallel runs, where Table 5.1 governs

A submain uses 2 × 95 mm² single-core copper cables with X-90 insulation. The earth fault current is 20 kA for 0.2 s. Set Construction to Single-core, Active size and Parallel runs to match, then switch on Earth Fault with XLPE or elastomer X-90 (90 °C) and enter 20 kA for 0.2 s.

Table 5.1 is read with 190 mm² of active, which gives a 95 mm² earth. The fault needs only 62.59 mm² (K 142.9), so the table governs and the earth to install is 95 mm² copper.

A small circuit near a strong supply, where the fault raises the earth

A 16 mm² multicore V-75 copper circuit leaves a board where the earth fault current is 3 kA, cleared in 0.1 s. With Earth Fault off, the calculator gives the Table 5.1 earth of 6 mm² copper. Switch it on with those values and the result changes:

Earth size for 16 mm² copper actives
RowEarth Fault offEarth Fault on
Total active area16 mm²16 mm²
Table 5.1 earth6 mm²6 mm²
K–111.2
Adiabatic minimum–8.53 mm²
Earth to install6 mm² copper10 mm² copper

The adiabatic minimum of 8.53 mm² is above the 6 mm² Table 5.1 size, so the fault check governs and the earth to install is 10 mm² copper. If the multicore cable's own earth core is smaller than that, the circuit needs a separate, larger earth, a faster device or a lower fault current at that point.

Best practice and AS/NZS 3000 Table 5.1 references

  • The fault check only raises the earth. Table 5.1 is the floor; a low fault current never lets you go below it.
  • Start the earth hot. An earth laid up with the actives runs at their temperature, so the calculator starts the fault at the actives' maximum operating temperature.
  • Check the fault loop next. A large enough earth for heat can still be too long for the device to trip in time. Run the circuit through the fault loop impedance calculator, or size the whole cable in the cable size calculator, which does all three checks.
  • Size earths for aluminium actives from the aluminium column. The earth is copper either way, and the aluminium column gives a smaller earth for the same active size.

Common earth sizing mistakes

  • Reading Table 5.1 with one run of a parallel group

    Enter the number of Parallel runs so the table is read with the total active area, as Clause 5.3.3.1.2 requires.
  • Leaving the Earth Fault check off near the switchboard

    Small circuits close to a strong supply are where the adiabatic check raises the earth. Turn it on whenever you know the fault current.
  • Using the copper column for aluminium actives

    Set Conductor to Aluminium so the calculator reads the aluminium column.
  • Treating Table 5.1 as the whole answer

    The table is a minimum. The fault current and the fault loop impedance can both require a larger earth.
If you set the earth size by hand in a cable calculation, keep it at or above the size this calculator gives, and record the fault current and clearing time it was checked against.

FAQ

What size earth cable do I need for my active conductor?

Start from AS/NZS 3000:2018 Table 5.1, which gives the minimum copper protective earth for each active size and material. Enter the active size in the earth cable size calculator and the Table 5.1 earth row shows it. Then check the fault current and the fault loop impedance, which can both call for a larger earth.

Should I leave the Earth Fault switch on?

Yes, whenever you know the earth fault current and the clearing time. With the switch off the calculator reads Table 5.1 only, which can be too small for a cable close to a strong supply. The check never makes the earth smaller than the table.

Why is the earth bigger than Table 5.1 says?

The Earth Fault check found that the Table 5.1 size cannot carry the fault current for the clearing time without overheating, so it raised the earth to the next standard size above the adiabatic minimum. The checks list in the result says the fault current governs.

Does the calculator give one earth per parallel run?

It sizes the earth from the total active area and shows the earth to install, which may be a single earth for the group. Run the earth so it follows the actives and stays within the fault loop impedance limit for the circuit.

Try the Earth Cable Size Calculator on your own circuit

Free to use, no account needed. Sign up to save calculations to projects and download the PDF reports.