How to use the cable short-circuit calculator

Check that a cable survives the fault until the protection clears it, with the adiabatic equation.

Updated 1 Nov 2026 · Reviewed by Suheib Sherif, electrical engineer

What the cable short-circuit calculator does

During a short circuit the current through a cable can be hundreds of times its rating. The protective device clears it in a fraction of a second, but until it does, the conductor heats up fast enough to damage the insulation. The free cable short-circuit calculator checks whether a conductor survives that heat, using the adiabatic equation of AS/NZS 3008.1.1:2025:

The energy the fault lets through () must not exceed what the conductor can absorb before the insulation reaches its limit (). The calculator gives the pass or fail, the minimum conductor size and how long the cable can carry the fault.

Use the cable short-circuit calculation when you:

  • connect a small cable close to a large transformer or main switchboard, where fault levels are high;
  • reuse an existing cable on a new, stronger supply;
  • choose between V-75 and X-90 insulation, or between two protective devices with different clearing times.

Before you start: fault current and clearing time

  • Prospective short-circuit current at the origin of the circuit, in kA: from the switchboard's fault level, the network operator, or an upstream fault calculation.
  • Clearing time in seconds: from the protective device's time-current curve at that current.
  • The conductor: copper or aluminium, insulation type and size in mm².

How to check cable short-circuit withstand, step by step

  1. 1

    Describe the conductor

    In the Conductor card choose the Conductor material (Copper or Aluminium) and the Insulation: Thermoplastic V-75 (PVC, 75 °C), XLPE or elastomer X-90 (90 °C) or Fire rated (110 °C). The insulation sets both the starting temperature and the limit temperature, and so K. Then pick the Conductor size, 1 mm² to 630 mm².

    Cable short-circuit calculator with the Conductor card set to copper V-75 16 mm² and the Fault card at 6 kA for 0.1 s
  2. 2

    Enter the fault

    In the Fault card enter the Prospective short-circuit current in kA. The hint reminds you to use the maximum, at the origin of the circuit. Enter the Clearing time in seconds, read from the device's curve; the field accepts 0.01 s to 5 s.

  3. 3

    Read the withstand check

    The Short-Circuit Withstand card updates as you type. The next section explains each row.

    Short-Circuit Withstand result card with the minimum size, smallest standard size, K factor, let-through I²t and withstand K²S²

Reading the short-circuit withstand result

The headline reads Conductor withstands the fault when it passes, or 1 check fails when it does not, with the size, material, current and time underneath. The rows are:

  • Minimum size (): the smallest cross-section that survives, to two decimals.
  • Smallest standard size: the next size on the ladder at or above the minimum. It turns red, saying the chosen size is too small, when the check fails.
  • (Table 5.1) and Temperature rise: the constant and the start and limit temperatures it is read for.
  • Let-through and Withstand : the two sides of the equation in A²s.
  • Withstand current for the entered time, and Withstand time at the entered current: how much headroom the cable has, either way.

Worked example: a 16 mm² cable at 6 kA

A 16 mm² copper cable with Thermoplastic V-75 (PVC, 75 °C) insulation is fed from a board with a prospective fault of 6 kA, and the upstream device clears it in 0.1 s. With those values entered the card shows 1 check fails:

Short-circuit withstand at 6 kA for 0.1 s
Row16 mm² V-75 PVC25 mm² V-75 PVC16 mm² X-90 XLPE
K (Table 5.1)111.2111.2142.9
Temperature rise75 → 160 °C75 → 160 °C90 → 250 °C
Minimum size17.06 mm²17.06 mm²13.28 mm²
Let-through I²t3.60 × 10⁶ A²s3.60 × 10⁶ A²s3.60 × 10⁶ A²s
Withstand K²S²3.17 × 10⁶ A²s7.73 × 10⁶ A²s5.23 × 10⁶ A²s
Withstand current for 0.1 s5.63 kA8.79 kA7.23 kA
Withstand time at 6 kA0.088 s0.215 s0.145 s
ResultFailPassPass

The 16 mm² V-75 conductor needs at least 17.06 mm², so the smallest standard size is 25 mm². It can only carry 6 kA for 0.088 s, less than the 0.1 s the device takes. Two changes in the calculator fix it:

  • Set Conductor size to 25 mm². The withstand rises to 7.73 × 10⁶ A²s and the cable lasts 0.215 s at the fault current.
  • Keep 16 mm² and change Insulation to X-90. K rises to 142.9 because the limit temperature is higher, the minimum falls to 13.28 mm², and the cable passes with 0.145 s of withstand.

A faster device is the third option: enter its clearing time and see whether the original size passes.

Best practice and the adiabatic equation in AS/NZS 3008

  • Take the clearing time from the device. Read it from the time-current curve at the prospective fault current, not from a disconnection-time table.
  • Use let-through energy for very fast devices. Below about 0.1 s, compare the manufacturer's let-through I²t with the Withstand K²S² row instead of entering a time.
  • Check at the start of the cable. The fault at the origin is the largest; the far end has the most impedance and the lowest current.
  • Run it inside the cable sizing. The cable size calculator does this check for the active and the earth together with current rating, voltage drop and fault loop.

Common short-circuit mistakes

  • Entering 0.4 s or 5 s by default

    Those are disconnection-time limits. The device usually clears a large fault much faster, or much slower near its overload region. Use the curve.
  • Using the fault current at the far end

    The adiabatic check uses the maximum prospective current at the origin of the circuit.
  • Starting the fault cold

    A conductor at ambient temperature has a higher K. The calculator starts at the insulation's maximum operating temperature; do the same in a hand check.
  • Picking the minimum size instead of a standard size

    The Minimum size row is a calculated cross-section. Install at least the Smallest standard size shown below it.
For fire rated cables, treat the Fire rated (110 °C) option as a design check and confirm the short-circuit rating against the manufacturer's data sheet.

FAQ

Why does the calculator start the fault at the insulation's maximum temperature?

A fault can happen while the cable is carrying full load, so the conductor is assumed to be at its maximum operating temperature when the fault starts: 75 °C for V-75 PVC, 90 °C for X-90 XLPE. Starting colder would give a higher K and overstate the withstand.

My cable fails the short-circuit check. What can I change?

Use a larger conductor, an insulation with a higher K such as X-90 instead of V-75, or a protective device that clears the fault faster. A current-limiting device with a published let-through I²t can also be checked against the K²S² the calculator shows.

Is the 0.4 s disconnection time the right clearing time to enter?

Usually not. 0.4 s is a maximum disconnection time for some final subcircuits, not the time the device takes at the fault current. Read the clearing time from the device's time-current curve at the prospective fault current.

Does this check the earth conductor too?

No, it checks the conductor you describe, normally the active. The earth carries the earth fault current and is checked with the earth cable size calculator, which applies the same adiabatic equation with copper K.

Blog

Read more on the method

Try the Cable Short-Circuit Calculator on your own circuit

Free to use, no account needed. Sign up to save calculations to projects and download the PDF reports.