Generator Sizing Calculator
Size a generator set from the running load and the largest motor's start
How It's Calculated
Two checks set the size, and the larger one governs.
Running load
The largest motor is included at its input kVA, its output divided by efficiency and power factor. Adding the loads as vectors rather than adding their kVA keeps loads at different power factors from being overstated.
Motor starting
The largest motor starts last, with everything else running. The generator's transient reactance and the motor's starting kVA act as a voltage divider, which gives the initial dip. This is a first-pass estimate: it ignores the voltage regulator's recovery, the low power factor while starting and the engine's load step capability (ISO 8528-5 performance classes), all of which the generator manufacturer's sizing software covers. Confirm the set with the manufacturer before ordering.
Worked Example
Loads of 20 kW at a power factor of 0.95 and 40 kW at 0.85, plus a 22 kW motor (efficiency 92%, power factor 0.85) started direct on line; 80% loading limit, 15% dip, :
- Running: ;
- Motor: 28.1 kVA running × 6 = 168.8 kVA starting
- Starting: 168.8 × 0.25 × 0.85 / 0.15 = 239.1 kVA
- Motor starting governs, so the next common size is 250 kVA, with a 14.4% dip
Starting the same motor star-delta brings the starting check down to about a third, and the running load (125 kVA set) decides the size instead.
Typical Starting Currents
The calculator's defaults, as multiples of the motor's full load current. Use the motor's locked-rotor current or the starter's current limit setting when you have them.