Voltage Rise Calculator Australia
Calculate voltage rise for solar PV, generators, and regenerative loads per AS/NZS 3008.1.1:2025
How it's calculated
The AS/NZS 3008.1.1:2025 Method
The calculator above runs the full CableHero engine, the same one behind saved calculations and PDF reports. These are the checks it makes, with the numbers for the example it opens with.
1. Current-carrying capacity
AS/NZS 3008.1.1:2025 Clause 2.3.1, Section 3 tables; correction factors Clause 3.5
is the tabulated current-carrying capacity of the cable for its installation method (for example Table 3.15 for thermoplastic two-core cables), the design current and the product of the correction factors: grouping (Clause 3.5.2, Tables 3.33 to 3.43), air or soil temperature (Clause 3.5.3, Tables 3.44 and 3.45), depth of laying (Clause 3.5.4, Tables 3.46 and 3.47) and soil thermal resistivity (Clause 3.5.5, Table 3.48). The smallest size that passes, and then passes every check below, is selected.
2. Voltage rise
AS/NZS 3008.1.1:2025 Clauses 2.3.2, 4.3, 4.4 and 4.5
is the a.c. resistance at the conductor's operating temperature (Clause 4.4, read from Tables 4.1 to 4.13), the reactance, the load power factor and the route length in metres. is the three-phase value per Clause 4.3; a single-phase circuit has two conductors carrying the current, so its drop is times it (Clause 4.5). d.c. circuits use (Clause 4.7).
Voltage rise is the same calculation with the current flowing the other way, from an inverter, battery or generator back towards the supply. Grid-connected inverters are limited to 2% (AS/NZS 4777.1, as set out in AS/NZS 3008.1.1:2025 Clause 4.1.2), measured from the inverter terminals to the main switchboard, or to the point of supply without high-export-voltage protection.
3. Short circuit and fault loop
AS/NZS 3008.1.1:2025 Clause 5.3; AS/NZS 3000:2018 Clause 5.7.4 and Appendix B5.2.2
The active and earth conductors must withstand the prospective fault current for the clearing time ( from Table 5.1). is the resistance of the active and earth conductors over the route; dividing by 0.8 allows for the 20% of the loop impedance upstream of the circuit. must not exceed , where is the current that trips the device instantly (for example for a Type C circuit breaker), so the device clears an earth fault in time.
Understanding Voltage Rise in Electrical Installations
What is Voltage Rise?
When an installation exports power, current flows from the local source towards the point of supply. The cable impedance then raises the voltage at the source end above the grid voltage. Inverters and generators must stay within their overvoltage limits, so voltage rise is a design constraint in its own right.
Voltage Rise vs Voltage Drop
- Voltage Drop: current flows from the supply to a load, lowering the voltage at the load
- Voltage Rise: current flows from a source to the supply, raising the voltage at the source
- Same Formula: both use the AS/NZS 3008.1.1:2025 mV/A.m method
- Different Limits: drop is limited to 5% by AS/NZS 3000:2018; rise from grid-connected inverters to 2% by AS/NZS 4777.1
When Does Voltage Rise Occur?
Solar PV Systems
- Large commercial solar installations
- Long cable runs from inverter to the main switchboard
- Installations at the end of long distribution feeders
Generators
Standby and prime generators exporting into the installation or the grid.
Regenerative Drives
Variable speed drives that return braking energy to the supply.
Battery Storage Systems
Batteries discharging into the installation or exporting to the grid.
The Voltage Rise Formula
Voltage Rise Limits
AS/NZS 3008.1.1:2025 Clause 4.1.2 sets out the AS/NZS 4777.1 limits for grid-connected inverter energy systems:
- With protection against high export voltages: at most 2% of the nominal supply voltage from the inverter output terminals to the connection to the installation (typically the voltage-sensing terminals at the main switchboard)
- Without that protection: at most 2% in total from the inverter output terminals to the point of supply
- Check your distributor's connection requirements for additional limits
AS/NZS 3008.1.1:2025 Voltage Drop Values
Use these values for voltage rise calculations. Three-phase Vc in mV/A.m for thermoplastic (V-75) multicore cables with conductors at 75°C, worst-case power factor (Tables 4.17 and 4.22); single-phase is 1.155 times it (Clause 4.5).
Important: Voltage rise and voltage drop are checked separately against their own limits. Check with your distributor for any additional connection requirements.
Frequently Asked Questions
Voltage Rise Questions Answered
Guides

