Protection Coordination Calculator

Time-current curves and discrimination to AS/NZS 3000:2018

How to use
Create a free account to save to a project Sign up to save

Study

%

AS/NZS 3000:2018 cl. 2.5.7.2.2: discrimination need not be shown above the arcing fault current, often 30–60 % of the prospective current. Blank checks up to the full fault level.

Generic standard curves. Results are indicative; confirm selectivity in the instantaneous region with the manufacturers' tables.

C63 MCB

Upstream

Manufacturer curves and selectivity tables arrive as licensed data; until then use the generic types or a custom curve.

kA

Icn / Icu from the nameplate; blank skips the check

kA

prospective three-phase fault at this board, from the cable sizing calculation's fault level

C20 MCB

Downstream

Manufacturer curves and selectivity tables arrive as licensed data; until then use the generic types or a custom curve.

kA

Icn / Icu from the nameplate; blank skips the check

kA

prospective three-phase fault at this board, from the cable sizing calculation's fault level

A

Iesc at the far end of the circuit, from the cable sizing calculation

Upstream first. Each device is compared with the one below it.

Coordination

1 check to confirm

2 devices · 1 pair · Ik 6 kA

  • Discrimination C63 → C20: Selective up to 315 A, the upstream C63 MCB's lowest instantaneous pickup (5 × In). Above that both devices trip instantaneously: confirm with the manufacturers' selectivity tables.
  • Disconnection C20: The minimum earth-fault current of 300 A reaches Ia = 200 A (Table 8.1, the upper instantaneous limit), so the MCB trips instantaneously, within the required 0.4 s.
  • Breaking capacity C63: 6.0 kA ≥ 6.0 kA
  • Breaking capacity C20: 6.0 kA ≥ 6.0 kA
C63 → C20 selectivity limit315 A
GradePartial · limited by upstream instantaneous
AS/NZS 3000:2018Not required (≤ 80 A), cl. 2.5.7.2.3

Selective up to 315 A, the upstream C63 MCB's lowest instantaneous pickup (5 × In). Above that both devices trip instantaneously: confirm with the manufacturers' selectivity tables.

Ief 300 A vs Table 8.1 Ia (C20)300 A ≥ 200 A
Zs max (Table 8.1, governs)1.15 Ω
Clearing (modelled curve)0.01 s
Zs max (modelled curve)1.55 Ω
Breaking capacity (C63)6.0 kA ≥ 6.0 kA
Breaking capacity (C20)6.0 kA ≥ 6.0 kA

Indicative: generic curves; the instantaneous region needs the manufacturers' tables.

Time-Current Curves

kA
undetermined: needs manufacturer tables0.4 sIef 300 AIk 6.0 kA · C63, C20101001 k10 k0.010.11101001 00010 000Current (A) at 400 VTime (s)

Frequently Asked Questions

Protection Coordination Questions Answered

What is discrimination and why does AS/NZS 3000:2018 ask for it?

Discrimination (selectivity) means that on a fault only the protective device nearest the fault opens, so the rest of the installation stays on. AS/NZS 3000:2018 clause 2.5.7.2 requires it where loss of supply would cause danger or serious inconvenience, and deems it met by ratios between device ratings in some cases. The calculator checks it by comparing the downstream device's slowest clearing time with the upstream device's fastest trip at every current up to the fault level.

Why are the results indicative?

The curves are the generic zones the device standards allow (AS/NZS 60898.1 for MCBs, IEC 60947-2 for MCCBs and air circuit breakers, IEC 60269 for gG fuses), not a particular manufacturer's curves. Real devices sit inside those zones, and in the instantaneous region, where both breakers trip in a few milliseconds, only the manufacturers' selectivity tables can confirm discrimination. The calculator marks that region as undetermined rather than guessing.

Which devices are modelled?

Miniature circuit breakers with B, C or D curves; thermal-magnetic MCCBs with adjustable Ir and Im; electronic trip units with long-time, short-time (with I²t on or off) and instantaneous stages on MCCB or ACB frames; gG fuses from 16 A to 1250 A; and custom devices from points you enter, either a minimum and maximum curve or one nominal curve with a tolerance.

How is the cable damage curve drawn?

From the adiabatic equation t = (kS / I)², where S is the conductor cross-section and k comes from the K table for the conductor and insulation in the cable's edition (AS/NZS 3008.1.1:2025 Table 5.1, or AS/NZS 3008.1.1:2017 Table 52), starting at the insulation's maximum operating temperature. The protective device must clear every current from about 5 s down to the fault current faster than the cable reaches its limit, and its let-through energy at the fault current must stay below k²S².

Is the protection coordination calculator free?

Yes. Anyone can run a study of two devices without an account. A free account saves one study to a project; a subscription saves as many as you need, with up to eight devices each.

Reviewed by Suheib Sherif, electrical engineer at CableHero. The calculator is a design aid: the designer remains responsible for checking the installation against the standards.

Guides

Learn the method

How to use this calculator

Plot the upstream and downstream devices and check they discriminate across the fault range.

Read the guide: How to use the protection coordination calculator

More free tools

Other calculators

Size the Cables Too

Check the cable each device protects with an AS/NZS 3008.1.1:2025 cable size calculation, and keep both in the same project.