How It's Calculated
The current follows from the real power, the voltage and the power factor. For AC the power factor turns the real power (kW) into the apparent power (kVA) that the current actually carries:
- Three-phase: I = P × 1000 / (√3 × VL × cos φ), with VL the line-to-line voltage
- Single-phase: I = P × 1000 / (V × cos φ), with V the phase-to-neutral voltage
- DC: I = P × 1000 / V
The apparent power is S = P / cos φ and the reactive power Q = √S² − P². The three-phase formula assumes a balanced load, the same current in each line.
Worked Example
A 10 kW load on a 400 V three-phase supply at a power factor of 0.8:
- I = 10 × 1000 / (1.732 × 400 × 0.8) = 18.04 A per line
- S = 10 / 0.8 = 12.5 kVA, Q = 7.5 kVAr
- The same 10 kW on 230 V single-phase draws 54.3 A