Battery Storage Sizing Calculator
Battery capacity, modules, inverter and cable currents for backup, daily cycling or off-grid, with the AS/NZS 5139 voltage class
Battery capacity, module count, inverter size and cable currents for a home or small commercial battery, with the AS/NZS 5139:2019 + A1:2025 voltage class.
How It Works
Sizing a Battery in Four Steps
Worked Example
10 Hours of Backup for the Essentials
A home uses 12 kWh a day on its critical circuits, an average of 0.5 kW, and wants 10 hours of backup from LFP modules of 5.12 kWh (51.2 V) through a 5 kW single-phase inverter, with a 4 kW peak load.
The loads need 0.5 kW × 10 h = 5.0 kWh. At 96 % inverter efficiency the battery delivers 5.21 kWh. Sized for 90 % depth of discharge and 70 % capacity at end of life, it needs 5.21 ÷ (0.90 × 0.70) = 8.27 kWh nominal.
Two modules (10.24 kWh) cover that, and their 5.12 kW of discharge covers the 4 kW peak (4.17 kW at the battery). At end of life they still give 6.45 kWh usable, about 12.4 hours of backup. The DC cable carries up to 5 kW ÷ 0.96 ÷ 44.8 V = 116 A, the AC cable 5 kVA ÷ 230 V = 21.7 A, and at 57.6 V maximum the battery is DVC-A.
Frequently Asked Questions