Cable SizingBy Ahmed Tayeh

EV Charger Cable Size: Sizing Home and Commercial EV Charger Circuits in Australia

A 7 kW and a 22 kW charger are both 32 A circuits, but the cable they need depends on the route length, the voltage drop allowance and the fault level. Here is the full check, step by step.

EV Charger Cable Size: Sizing Home and Commercial EV Charger Circuits in Australia

The EV charger cable size for a typical 7 kW single-phase home charger or a 22 kW three-phase charger starts at 6 mm² copper, because both draw 32 A and need a 32 A circuit. Whether 6 mm² is enough depends on three things the current alone does not tell you: the route length (voltage drop), the installation method (current rating) and the prospective fault current at the switchboard (short-circuit withstand). On a 25 m run in conduit the single-phase charger needs 10 mm² to stay within a 2% voltage drop allowance.

Before any of that, the supply itself has to have room for another 32 A. This guide works through both, in the order a designer should: maximum demand first, then the circuit, with worked numbers from the CableHero engine for a 7 kW and a 22 kW charger.

What a charger draws

Home chargers in Australia are mostly single-phase units rated around 7 kW, and three-phase units rated around 11 kW or 22 kW. Converting with the formulas in our kW to amps guide, at a power factor close to 1:

  • 7 kW single-phase: a 32 A charger, 32 × 230 = 7.36 kW.

  • 11 kW three-phase: 11 000 / (√3 × 400) = 15.88 A per line, a 16 A charger.

  • 22 kW three-phase: 22 000 / (√3 × 400) = 31.75 A per line, a 32 A charger.

Two features make an EV charger different from most household loads. It runs at full current for hours at a time, so there is no short-duty allowance to lean on. And it tends to run in the evening, at the same time as cooking, heating or cooling, so it lands on top of the existing peak rather than filling a gap.

Step 1: check the maximum demand

AS/NZS 3000:2018 Appendix C, Table C1, has a load group for charging equipment associated with electric vehicles. In the CableHero Maximum Demand Calculator a single dwelling's charger takes its full connected load; there is no diversity for it. (Blocks of living units take 100%, 90% or 75% depending on the block size.)

Take a house assessed with Table C1 on a single-phase 230 V supply: 30 lighting points, 40 socket-outlet points, a 10 kW range, a 7.2 kW split system and a 3.6 kW storage water heater. The calculator gives 5 A + 15 A + 21.7 A + 23.5 A + 15.7 A = 80.9 A. Add the 32 A charger at full load and the maximum demand becomes 112.9 A, a 40% increase on one phase. A house with this much fixed load is already beyond what many single-phase services allow, so on a real job this result points straight to load management or a three-phase supply.

EV charger cable size starts with the supply: maximum demand of a house before and after a 7 kW or 22 kW charger, single-phase and three-phase

The same house on a three-phase supply, with the range on L1, the air conditioner on L2, the water heater on L3 and the lights and power split over L1 and L2, has a demand of 34.7, 36.5 and 15.7 A. Adding a 22 kW charger puts 31.75 A on every phase: 66.5, 68.2 and 47.4 A. Adding a 7 kW single-phase charger to the lightest phase, L3, gives 34.7, 36.5 and 47.7 A, and actually improves the balance.

What to do with the result:

  • Compare it with the supply. The consumer mains, the main switch and the service capacity offered by the network all have to cover the new maximum demand.

  • Put a single-phase charger on the lightest phase of a three-phase supply, not the one with a spare pole.

  • Consider load management if the numbers do not fit. Many chargers can reduce their current when the house load is high, which is cheaper than a supply upgrade. Whether a managed charger can be assessed at less than its full rating is a question for the network and the inspector, not for the calculation alone.

Network service and installation rules set the maximum single-phase load, whether a charger needs to be notified or approved, and when a three-phase supply is required. They differ between distributors, so check the current rules for the area before you promise a 7 kW charger on an existing single-phase service. For the residential method in more detail, see how to calculate residential maximum demand.

Step 2: work out the EV charger cable size

EV charger circuit from switchboard through a 32 A MCB and RCD to the charger, with the five checks that set the EV charger cable size

With the supply confirmed, the circuit itself has to pass four checks. The worked examples below use the same assumptions so you can compare them:

  • copper multicore cable, thermoplastic (PVC) insulation rated 75 °C, enclosed in conduit in air, no grouping or ambient derating;

  • a 25 m route from the switchboard to the charger;

  • a 32 A C-curve MCB, with the cable sized to the breaker rating;

  • a 2% voltage drop allowance for this circuit, leaving the rest of the 5% that AS/NZS 3000:2018 Clause 3.6.2 allows from the point of supply for the mains;

  • a prospective fault current of 3 kA and a fault time of 0.1 s at the switchboard (the calculator's defaults).

Worked example 1: 7 kW single-phase charger

  1. Current rating. From the single-phase multicore table of AS/NZS 3008.1.1:2025 (Table 3.15, enclosed), 4 mm² is rated 30 A, which is below the 32 A breaker. 6 mm² is rated 39 A, so 6 mm² passes on capacity.

  2. Voltage drop. At 25 m, 6 mm² drops 2.61%, over the 2% allowance. 10 mm² drops 1.47%, which passes.

  3. Fault loop impedance. A C32 MCB trips instantaneously at 7.5 × 32 = 240 A, so Zs must not exceed 230 / 240 = 0.958 Ω. The calculated Zs with 10 mm² is 0.242 Ω, which passes.

  4. Short-circuit withstand. At 3 kA for 0.1 s the active conductor needs at least 8.53 mm². 10 mm² passes, with a 4 mm² earth.

Result: 10 mm² active and neutral with a 4 mm² earth, rated 52 A, 1.47% voltage drop. If the run were 15 m instead, 6 mm² would pass voltage drop, but the 3 kA short-circuit check would still hold the cable at 10 mm².

Worked example 2: 22 kW three-phase charger

  1. Current rating. From the three-phase multicore table (Table 3.18, enclosed), 4 mm² is rated 25 A and 6 mm² is rated 33 A. 6 mm² passes the 32 A breaker with 1 A to spare.

  2. Voltage drop. Three-phase drop is far kinder: 6 mm² drops 1.30% at 25 m, inside the 2% allowance.

  3. Fault loop impedance. The maximum for a C32 is 0.962 Ω here (the engine works from the 400 V line voltage divided by √3); 6 mm² gives 0.399 Ω.

  4. Short-circuit withstand. The same 3 kA for 0.1 s needs 8.53 mm², so the calculator steps up to 10 mm² (0.73% drop, 4 mm² earth).

Here the short-circuit check, not the load, sets the size. If the prospective fault current at the board is actually 2 kA, the minimum falls to 5.69 mm² and 6 mm² with a 2.5 mm² earth passes every check. That is why it pays to enter the real fault level from the network or the upstream calculation rather than leaving a default.

Voltage drop against route length for 6 mm² and 10 mm² EV charger cables, single-phase and three-phase, with a 2% allowance

The chart shows why route length matters so much more on single-phase. With a 2% allowance, 6 mm² single-phase reaches its limit at about 19 m and 10 mm² at about 34 m; the three-phase cables go to roughly 38 m and 68 m. Detached garages and long carport runs are where single-phase chargers end up on 16 mm². Our guide to voltage drop limits in Australia explains how to split the 5%.

Protection for the charger circuit

  • Overcurrent: a dedicated circuit with an MCB matched to the charger's rated current (32 A for both examples), so Ib ≤ In ≤ Iz holds. A C curve is common; whichever curve you choose sets the maximum Zs, as our guide to MCB trip curves explains.

  • Earth fault: RCD protection, of the type the charger's installation manual specifies. Many chargers include DC fault current detection so that a standard type can be used upstream; others require a type that can handle DC fault currents. Check the manual before choosing the device.

  • Earthing: the protective earth sized with the active, checked for the fault as in our guide to earth cable size.

Commercial and multi-charger sites

A car park with several chargers is a submain design, not a set of individual circuits. The maximum demand comes from AS/NZS 3000:2018 Appendix C (Table C2 for non-domestic installations, or Table C1 for the common area of a block of units), grouped cables in the same tray or conduit need a grouping derating factor, and long submains will usually be governed by voltage drop. Load management across the chargers is often what makes the supply work. Run the submain through the Cable Size Calculator with the grouping factor, then size each final subcircuit from the submain's distribution board.

Common mistakes

  • Sizing the cable from the kW without checking the supply. The circuit can be perfect and the service still overloaded at 6 pm.

  • Assuming 6 mm² is always enough for 32 A. It is on capacity in conduit, but voltage drop on single-phase runs past about 19 m, and the short-circuit check at a higher fault level, can both push it to 10 mm².

  • Ignoring the installation method. Cable run through insulated ceilings or walls derates heavily. A 6 mm² that passes in conduit in air may not pass surrounded by insulation.

  • Adding the charger to the busiest phase of a three-phase supply because that is where the spare pole is.

  • Leaving the fault level at a guess. It decides the minimum conductor size, especially on short runs close to the transformer.

  • Choosing the RCD before reading the charger manual. The required RCD type depends on the charger's own DC fault protection.

FAQ

What size cable do I need for a 7 kW EV charger?

A 7 kW charger draws 32 A on a 32 A circuit. In conduit, 6 mm² copper carries it, but on a 25 m run 6 mm² drops 2.61% at 230 V, so with a 2% allowance you need 10 mm². Short runs and lower fault levels can stay at 6 mm²; long runs may need 16 mm².

What size cable for a 22 kW three-phase charger?

Also 32 A per line. 6 mm² four-core is rated 33 A in conduit and drops only 1.30% over 25 m. It passes completely at a 2 kA fault level; at 3 kA and 0.1 s the short-circuit check needs 10 mm².

Can I put a 7 kW charger on a single-phase supply?

Often, but check the maximum demand and the network's rules first. In our example house the charger took the demand from 80.9 A to 112.9 A on one phase. Load management, a smaller charge current or a three-phase upgrade are the usual answers when it does not fit.

Does the EV charger count in the maximum demand?

Yes. AS/NZS 3000:2018 Table C1 has a load group for EV charging equipment, and for a single dwelling the calculator takes the charger's full connected load.

Check your own charger circuit

Start in the Maximum Demand Calculator: choose Table C1, Single Domestic Dwelling, set the supply phases, enter the existing loads and add the charger under load group (j)(iv), then read the demand on each phase. The free calculator takes five loads without an account. Then open the Cable Size Calculator, enter 32 A (or the charger's rated current), the route length, the installation method, a 32 A MCB with its curve, your voltage drop allowance and the fault level at the board. It returns the smallest cable that passes capacity, voltage drop, fault loop and short-circuit, with the earth size. For the single-phase method in depth, see single-phase cable sizing, and for the fault check, fault loop impedance.

Work it out for your circuit

Free calculators, no sign-up needed.