How to check solar voltage rise with the voltage rise calculator

Size the AC cable from a solar inverter so the voltage rise stays inside the 2% limit.

Updated 1 Nov 2026 · Reviewed by Ahmed Tayeh, electrical engineer

What the voltage rise calculator does

A grid-connected solar inverter pushes current back towards the network, so the voltage at its terminals sits above the voltage at the switchboard. If that voltage rise is too large, the inverter sees high voltage and trips or throttles its output on sunny days. The CableHero voltage rise calculator sizes the AC cable from the inverter so the voltage rise calculation for solar stays inside the 2% limit, and checks the same cable for current rating, short-circuit withstand and earthing.

It is the cable size calculator with its threshold switched to Rise: the same AS/NZS 3008.1.1:2025 engine, the same cards and the same report.

The voltage rise calculator with the Rise tab selected, a 2% threshold and the Cable Size result showing the voltage rise

Before you start

  • The inverter's rated AC output current (or rated power), and whether it is single phase or three phase.
  • The cable route length from the inverter's AC terminals to the main switchboard, in metres.
  • The cable type and how it is installed (in conduit, clipped, in a roof space, in insulation).
  • The fault level at the switchboard, if you have it, for the short-circuit check.
  • Your distributor's inverter connection rules, in case they set a tighter rise than 2%.

How to check solar voltage rise step by step

  1. 1

    Enter the inverter output current

    In Electrical Load keep the Unit on Amps and type the inverter's maximum continuous AC output current as the Load. You can enter kW instead; leave the Power factor at 1 for an inverter exporting at unity, so the current shown underneath matches the datasheet.

  2. 2

    Switch the threshold to Rise

    In System Supply choose the Supply, enter the Length of run and the Voltage, then click Rise beside the threshold. The field becomes Voltage rise threshold and the Standard limit switches to 2% · grid-connected inverter. Its hint says where the limit is measured: from the inverter terminals to the main switchboard, or to the point of supply without high-export-voltage protection. Type a smaller value if your distributor requires one.

    System Supply card with the Rise tab selected, a 2% voltage rise threshold and the grid-connected inverter Standard limit
  3. 3

    Describe the cable and how it is installed

    Fill in Cable, Installation Method and Derating Factor as for any circuit. Inverter cables often run through hot roof spaces or alongside other circuits, so set the ambient and grouping honestly: a hotter conductor has a higher resistance and a larger rise. Enter the Fault level and Fault time for the switchboard end.

    The Distributed load switch is hidden in rise mode: the half-rating allowance is for load circuits only.

  4. 4

    Read the voltage rise

    The Cable Size card picks the smallest cable within the rise threshold. The summary's Voltage rise line shows the percentage against the limit; the Voltage rise row gives volts and percent.

    Cable Size result card for an inverter circuit showing the Voltage rise check against the 2% limit and the selected active and earth sizes

Reading the voltage rise result

A green Cable OK means the cable is within the rise threshold and passes the current, fault withstand and earthing checks. If you set the Active size by hand with the Manual switch (to check an existing cable, say), a rise above the threshold shows as a red Voltage rise line. The Operating temperature row explains small differences from a table lookup: a cable carrying well under its rating runs cooler and has a lower resistance.

Remember what the 2% covers. If the limit applies to the point of supply in your case, the consumer mains are part of the path, and the inverter cable gets only what is left after their rise at the inverter's output current.

Worked example: a 5 kW inverter 20 m from the switchboard

The public voltage rise calculator opens with this circuit: a single-phase inverter with a 21.7 A rated output (about 5 kW at 230 V), 20 m of two-core copper cable to the main switchboard, insulation Thermoplastic (75 °C), installation method Enclosed Wiring Enclosure In Air, fault level 1,500 A, and the 2% rise limit, which is 4.6 V at 230 V.

  • 4 mm² is rated 30 A, plenty for 21.7 A, but rises 2.01% over the run, and fails on voltage rise and short-circuit withstand.
  • 6 mm² is rated 39 A (17.3 A spare), runs at about 50.8 °C and rises 3.09 V (1.34%). It stays inside 2% for a run up to about 30 m.
Result: 6 mm² active with a 2.5 mm² earth. The current rating alone would have allowed a much smaller cable; voltage rise set the size.

Voltage rise best practice (AS/NZS 4777.1 2% limit)

  • Check your distributor's rules: network service and installation rules and inverter connection agreements can set a lower figure, or measure it to a different point. Enter their figure as the threshold.
  • Size for the inverter, not the array: the AC cable carries the inverter's output current. The d.c. string cables are sized separately; for those use DC with PV array circuit on, or the string voltage calculator for the string voltages.
  • Allow for growth: if a battery or a larger inverter is likely, size the cable for the larger output now. Upsizing the cable is cheaper at installation than later.
  • Mind the network voltage: sites with a high network voltage are the ones where inverters trip on overvoltage, so a cable that only just meets 2% leaves little margin. A size up costs little and keeps the inverter exporting.

Common voltage rise mistakes

  • Using the 5% voltage drop limit

    5% is the load-side voltage drop limit in AS/NZS 3000:2018. An inverter circuit uses the 2% rise limit: select the Rise tab.
  • Forgetting the consumer mains share

    Where the limit is measured to the point of supply, the consumer mains carry the export too. Take their rise off the 2% before sizing the inverter cable.
  • Entering a three-phase inverter as single phase

    A three-phase inverter's output is shared across three phases at 400 V. Entered as single phase with the total current, the rise is grossly overstated.
  • Using the panel or string current

    The AC cable carries the inverter's rated AC output current, from the datasheet.

FAQ

What is the voltage rise limit for solar in Australia?

AS/NZS 4777.1 limits the voltage rise from a grid-connected inverter to 2%, measured from the inverter's AC terminals to the main switchboard (or to the point of supply where there is no high-export-voltage protection). AS/NZS 3008.1.1:2025 Clause 4.1.2 points to that limit. Many distributors set their own rules for inverter connections, which can be tighter, so check your network's requirements.

What current do I enter for voltage rise?

Enter the inverter's rated continuous AC output current from its datasheet, not the panel or string current. For a single-phase 5 kW inverter at 230 V that is about 21.7 A. For a three-phase inverter, choose Three Phase and enter the current per phase at 400 V.

Is voltage rise calculated the same way as voltage drop?

Yes. The current flows the other way, but the volts lost along the cable are the same: current times the cable's impedance over the route length. The difference is the limit: 2% for the inverter circuit instead of a share of the 5% voltage drop limit for loads. The calculator's Rise tab switches the limit and labels the result Voltage rise.

Why does the calculator pick a bigger cable than the inverter current needs?

Because the 2% limit usually governs, not the current rating. In the worked example a 4 mm² cable is rated 30 A, well above the 21.7 A inverter, but rises 2.01% over 20 m, just over the limit, and also fails the short-circuit withstand check, so the calculator selects 6 mm².

Try the Voltage Rise Calculator on your own circuit

Free to use, no account needed. Sign up to save calculations to projects and download the PDF reports.